Regulations - Fire Service Regulations
3 |
Stand ingress and egressOften stands are not closed off by a wall on at least one side, have a limited floor area and are not intersected by an aisle. In such a situation, no further requirements are made in respect of the egress signage. In all other cases exhibitors must apply to the exhibition organisers for information about any further conditions that may apply.
|
5 |
ImportantEven when a certificate can be produced, the local fire brigade has the right to ask the stand builder or the exhibitor for a sample of a material for testing. The party requested is then under an obligation to supply the sample. The flame-proofing substance (saline solution) can harm clothing materials (colour change and shrinkage) and corrode some metals. |
|
5.1 |
Load-bearing elements of stand constructionThe load-bearing elements of the stand must be of stable construction and made of materials of fire propagation classes 1 or 2 (NEN standard 6065). In the case of certain stand types or methods of construction a municipal approval must have been granted on the basis of a strength calculation (in the case of a grandstand or two-storey stand) or construction method (in the case of steel strapping or wall anchors). |
|
5.2 |
Partition walls, decors and requisitesWalls, decors and requisites must be made of materials that are not easily flammable (classes 1 or 2, see NEN standard 6065). When engineered wood products (triplex and the like) are used and have a thickness of more than 3.5mm the material need not be flame-proofed; see also article 19.4 in this document. Materials such as hardboard, softboard, cardboard and plastic foam board must have been treated and flame-proofed, regardless of the thickness of the material. If treated material is alleged to be no longer easily flammable this must be demonstrated by means of a test. |
|
5.3 |
Wall-covering materialsWall-covering materials must have the properties of fire propagation classes 1 or 2 (NEN standard 6065). Even if the material does not meet the requirements of fire propagation classes 1 or 2, there are no strong objections to the use of unapproved materials (depending on the thickness of the material) provided they are glued to a base consisting of a material of fire propagation class 1 or 2 and non-flammable (water-based) adhesive is used. However, if unapproved material is used and not glued (i.e. other than as indicated above) consent will be given for its use only if the unapproved material covers a relatively small surface area of the wall. Unapproved material should be applied as an uninterrupted covering. Whether consent is obtained for the application of unapproved material depends on the assessment of the actual situation by the local fire brigade. Wall-covering materials, curtains and so forth that belong to fire propagation classes 1 or 2 may be draped in folds. Wall-coverings, decor and requisites must be kept free of possible ignition sources (spotlights, heat-producing equipment and so forth). The following types of wall covering are not permitted, unless the material belongs to fire propagation classes 1 or 2 (NEN standard 6065) and the smoke density does not exceed the permitted levels (NEN standard 6066):
|
|
5.4 |
The use of curtains in relation to doors and passagesSubject to certain conditions, curtains may be hung in passages between stands on to which aisles emerge and which by virtue of their location form part of an escape route in a particular area. In order to close off the stand visually, a partition structure may be placed at a distance of not less than ¾ of the width of the passage. To create the visual partition, strips of flannel with a width of 0.5m may be attached to a frieze and should have a floor clearance of 0.05m. If canvas, curtains or other furnishing materials are to be hung in front of emergency doors, they must be attached to the doors in such a way as not to obstruct free access. This means that curtains and the like must be attached to the door in such a way that the unlocking mechanism (handle or push bar) is visible and can remain unobstructed. Canvas, curtains or other furnishing materials may be attached only in such a way that the prescribed markings and directional arrows, whether in the form of transparent light fittings or otherwise, remain clearly visible. |
|
5.5 |
Floor coveringThe floor covering in stands and other areas accessible to the public must at least comply with NEN-EN standard 1775:2007 and NEN standard 1775/C2, classes 1 or 2. In the gangways, escape routes and stairwells, the floor covering must at least comply with fire propagation class 2, in accordance with NEN standard 6065. The floor and staircase covering must be laid in such a way that it cannot move or curl or roll up or expose visitors to the risk of slipping, tripping or falling. |
|
5.6 |
Types of paint and varnishOnly water-based paints or fire-retardant paints should be used in stand construction and for decorative objects, if this is necessary because materials listed under article 19 in this document are to be used. See also article 4.1 in this document. |
|
5.7 |
Reflective and transparent materialsIn the stands and other areas accessible to the public, glass mirrors may be used as wall covering if they are properly attached to a firm base. This means that the mirrors may not shatter even if subjected to considerable pressure. Vertical reflective surfaces consisting of taughtened plastic foil materials are permitted on condition that the material has been flameproofed during production and is of flame retardant quality. Mirrors made of glass or foil may not adversely affect the sense of direction of visitors, particularly as regards the location of exits. Mirrors may not be put up in gangways or an escape routes, unless they are interrupted at eye height. Mirrors made of glass sheeting or taughtened foil material may never be used as part of the structure of a ceiling. Glass panels in external walls or partition walls of a stand may be used only if made of safety glass or reinforced glass (see also article 19.6 in this document). Depending, among other things, on the nature of the exhibition, it may be necessary for glass panels in the walls of the stand bordering the gangways to be protected from pressure by means of sufficiently heavy wooden or steel rim guards at a height of approximately 0.80 m on the gangway side. Such provisions can be made mandatory by the local fire brigade. |
|
5.8 |
Stand furnitureLayout plans / Building Regulation art. 6.5.6 Explanation
The following rules apply to a theatre configuration:
|
|
5.9 |
Plants, flowers and shrubs as decorationsPlastic plants and shrubs and artificial flowers may be used for decorative purposes if they are classified in fire propagation class 2 in accordance with NEN standard 6065. If the greenery does not meet these requirements, it is permitted only to a very limited extent. This is a matter for assessment by the local fire brigade. |
6 |
Stand ceilingThe stand ceiling may consist of stretch fabric products, various types of sheeting material or metal modular panels.
|
7 |
Load-bearing structural elements of the standThe load-bearing elements of the stand should be structurally stable and the materials used should comply with fire propagation classes 1 or 2 in accordance with NEN standard 6065. |
8 |
Two-storey standsA design for a two-storey (double-decker) stand requires a permit from the RAI’s Permits Desk.
|
|
8.1 |
Ingress and egress (two-storey stand)The number of exits and staircases depends on the floor area of the first floor:
|
|
8.2 |
Straight staircases (two-storey stand)At the point where the staircase meets the upper deck the width of the deck must be at least equal to that of the stairs.
|
|
8.3 |
Spiral staircases (two-storey stand)A spiral staircase is permitted as an escape route only if no more than 10 people need to make use of it. If such a staircase is permitted, the diameter of the spiral must be at least 0.7 0m. |
|
8.4 |
Handrails (two-storey stand)Stairs must be fitted on both sides with sound and firmly attached handrails and must be closed off at the side up to the height of the railing. If the width of the staircase is more than 2.20 m the staircase must be divided by one or more sound and firmly attached handrails. The ratio of the division must be 5:10:5. |
9 |
Visitor area in the exhibition hallOne or more areas in an exhibition hall may be used as a pavement cafe, restaurant, cinema, demonstration area, concert hall or theatre with tiered seating, either as an independent unit or as part of an exhibition. Areas used for the above-mentioned purposes are subject to the rules specified in Article 4 in this document: 'General stand construction and decoration regulations'. The configuration of the seating must be arranged with due care and recorded in a seating plan. For details see
Article 5.8 in this document.
|
10 |
Electrical systems and stand lightingOnly electric lighting may be used for a stand and the electrical system may be installed only by certified electricians. If the system does not meet the relevant conditions of EWN and NEN standard 1010, NEN-EN standard 50107, NEN standard 3140 (fire brigade, insurers), it may not be connected to the power grid. Stand electrical cables should have a minimum core diameter of 2.5 mm2 (live wire 2.5 mm2 in tube is also permitted). The use of thinner cable is strictly forbidden, unless the electrician can show that it meets the requirements of NEN standard 1010. Note on electrical systems and stand lighting:
Safety measures for neon light fittings and systems should comply with standard NEN-EN 50107. Notwithstanding these rules of NEN standard 1010, the following implementation rules apply in the Convention Centre:
|
11 |
Gas cylindersThe presence and/or use of compressed or liquefied flammable gases in a convention centre is permitted only after written consent has been obtained from the chief officer of the local fire brigade. Such consent may be made conditional on compliance with one or more of the following provisions:
|
13 |
Exhibiting toxic substancesExhibiting toxic substances, whether or not in their original packaging, is in principle prohibited unless:
|
14 |
Substances and equipment that emit ionising radiationSubstances and equipment that emit ionising radiation (i.e. radioactive substances or x-ray equipment) are covered by the Nuclear Energy Act. Without a permit the possession and/or use of these substances or equipment is prohibited.
|
15 |
Laser lightThe use of laser light must always be notified to the exhibition organisers. The issue of a permit may always be made conditional, depending on the nature of the laser (wavelengths, energy, pulsed or non-pulsed). Often the consent of the local fire brigade is also required. The check on compliance with the conditions specified in the permit is carried out by the Ministry of Social Affairs and Employment and/or the Labour Inspectorate. Class 1 - Safe sources of radiation Class 2 - Sources of radiation that are not entirely safe Class 3 - Dangerous sources of radiation
Class 4 - Very dangerous sources of radiation |
16 |
Operating welding equipment, combustion engines etc.All combustion engines, welding equipment, equipment that involves naked flames and so forth which is demonstrated in the Convention Centre must be notified to the exhibition organisers. Without exception, a permit (exemption) from the chief officer of the local fire brigade is required for these forms of demonstration. |
17 |
DemonstrationsAll demonstrations of equipment in the Convention Centre should be notified to the exhibition organisers. Not all forms of demonstration are permitted by exhibition organisers. For many forms of demonstration conditions will be imposed by the local fire brigade in a permit (exemption). Applicants for such a permit should apply early so as to ensure that when they receive the permit they still have sufficient time in which to satisfy the conditions and are thus not barred from giving demonstrations in the days before the conditions are met. |
18 |
Storage of packagingExhibitors are never permitted to store packaging material etc. behind or next to the stand. This is because such material is easily flammable. Packaging may, however, be stored in an unused part of the Convention Centre if appropriate safety measures have been taken in consultation with the exhibition organisers and the local fire brigade, for example:
Permission may be given for a day’s supply in consultation with the fire brigade. In the permit (exemption) issued by the local fire brigade, restrictive conditions may be imposed as regards the size of the supply. |
19 |
Stand construction materials and the permitted manner of applicationStand construction material
Manner of use
1. Softboard
The material must be coated on all sides (surfaces) with a fire-retardant paint or varnish.
2. Hardboard
The material must be coated on at least one side with a fire-retardant paint or varnish (on both sides if the stand is not adjacent to
another stand).
3. Wood or fibreboard thinner than 3.5 mm
The material must be coated on at least one side with a fire-retardant paint or varnish (on both sides if the stand is not adjacent to
another stand).
4. Wood or fibreboard thicker than 3.5 mm
The material may be applied without special treatment.
5. Glass used vertically
Safety glass or glass with embedded crosswire reinforcement with a maximum mesh width of 16 mm in a wooden or metal frame with a minimum depth of 15 mm.
6. Glass used horizontally
Safety glass or glass with embedded crosswire reinforcement with a maximum mesh width of 16 mm in a wooden or metal frame with a minimum depth of 15 mm.
7. Plastic sheeting made of expanded plastic and plastic rubbers
The material must be of a quality that is not easily flammable and should comply with NEN standard 6065, fire propagation
class 1 or 2, see article 5.3 in this document.
The material may not emit large quantities of smoke and/or gases or vapours that are harmful to health in accordance with NEN 6066, see article 4.1 in this document. The material may not drip when heated. 8. Foil material (metal)
The material may not be used without special treatment.
9. Plastic foil material
The material must have been flame-proofed in the production process and should comply with NEN standard 6065, fire propagation class 1 or 2.
The foil may never be used as a cover or ceiling for a stand. Combustible foil may be used only if it is affixed (using a non-inflammable water-based adhesive) to a base of non-inflammable material or to one of the materials referred to under article 5.3 in this document. 10. Paper products such as crepe paper, wallpaper, decorations and so forth
The material must be flame-proofed and comply with NEN standard 6065, fire propagation class 1 or 2.
11. Straw bales, cardboard, rushes, straw, mats, raffia, hay and so forth
The material must be flame-proofed and comply with NEN standard 6065, fire propagation class 1 or 2.
Note: The material must be immersed in a fireretardant agent for at least 2 x 24 hours in order to meet the requirements 12. Fabric made of natural fibres such as cotton, linen, jute, wool and so forth
This material must have been flame-proofed and should comply with NEN standard NEN 6065, class 1 or 2.
13. Fabric made of synthetic fibres
The material must have been flame-proofed during the production process and should comply with NEN standard 6065, class 1 or 2.
The material may not drip when heated. Note: Combustible fabric made of synthetic fibres will seldom fulfil the class requirements as a result of flame-proofing. 14. Fabrics used vertically such as tarpaulins, stand ceiling cover and so forth
The material may be used only in the manner indicated in the conditions referred to in article 19.12 and 19.13 in this document and the fabric must be taughtened using metal wires with a thickness of 0.3 mm; the wires must run in one direction and be at a minimum distance of 1m from one another.
15. Carpeting as wall covering
The material must have been flame-proofed during the production process and should comply with NEN standard 6065, class 1 or 2.
The material may not emit large quantities of smoke and/or gases or vapours that are harmful to health in accordance with NEN 6066, see article 4.1 in this document. |
20 |
Specific fire service regulations on tents/marqueesA tent or marquee may not be erected in such a way that the fire brigade cannot gain immediate access to fire hydrants and other water supplies. The structure and erection of the tent or marquee must be to the satisfaction of the Building Control Department of the urban district and in keeping with the Building Decree. For the placement of a tent or marquee an 'object' permit is required (for applications, see Annex 5: Permits Handbook). Load-bearing structures, floors and so forth may not be made of materials that emit large quantities of smoke or gases harmful to health immediately after a fire breaks out. The layout of the tent or marquee must be to the satisfaction of the fire brigade in terms of fire safety. Where the seating is arranged in rows the free space between the rows must be at least 0.4 m, measured between the plumb lines at the point where the rows are closest together. If tables have been placed between seats in a row, the free space must continue at the point where the tables are placed.
Doors in emergency exits must open in the direction of the escape route and, if they are closed, must be capable of being opened by one simple hand action. If curtains, net curtains or other furnishing materials have been hung in front of exits or emergency exits, these must be attached in such a way that they do not obstruct escape routes. The entrances, passageways, exits and so forth must be kept free of obstacles across their full width at all times. If there is a difference in height of more than 40 cm between the floor of the tent or marquee and the level of the surrounding terrain, ramp elements with a non-slip surface should be placed in order to bridge the gap. These should be at least 50 cm wider than the width of the exit. The electrical installations in the tent or marquee must comply with the provisions of NEN standard 1010 and with any local connection conditions. An electrical emergency and transparent lighting system must have been installed in the tent or marquee and powered by a power source separate from the normal power supply. The power source(s) of the emergency and transparent lighting system must be such that the light fittings can emit light at full strength for 30 minutes and the light strength measured at floor level is 1 lux. While members of the public are in the tent or marquee the transparent light fittings must be on at all times. Emergency lighting, transparent light fittings and other escape route markings must remain properly visible at all times. Portable fire extinguishers must be present in the tent or marquee in what the fire brigade considers to be sufficient numbers. The fire extinguishers must be positioned so that they are easily visible and ready and accessible for immediate use. The position of the fire extinguishers must also be indicated by pictograms. Any materials used for furnishing, decoration and so forth in the tent or marquee must not be easily flammable or must have been flame-proofed. Ceiling decorations must be hung at a height of at least 2.5 m above the floor, and curtains and other furnishings that hang vertically should be kept at least 0.10 m clear of the floor. Decorations, furnishings and so forth should be kept clear of spotlights and other heat-emitting equipment to ensure that the material cannot catch fire. Floor covering should be laid in such a way that it cannot move or curl or roll up or expose those present in the tent or marquee to the risk of slipping, tripping or falling. The tent or marquee must be clean and in good condition. Rubbish, packaging and so forth must be put into lockable containers made of non-combustible material. If a tent is erected as a smoking area with the express written consent of the Permits Desk, only self-extinguishing ashtrays or sand buckets may be placed. These should then be regularly emptied, in any event daily, and the contents deposited in lockable ash containers made of non-combustible material. The following may not be present in a tent or marquee:
|
21 |
Specific fire service regulations on barbecuesAn organiser or exhibitor is not permitted to hold a barbecue in or near the RAI building. However, RAI Catering may be able to arrange a barbecue subject to the following conditions:
|
22 |
SourcesStatutory regulations and standards:
|
MK/221015